Diesel rotary UPS (DRUPS)
A backup machine combining a flywheel, an alternator and a diesel engine in one unit, to carry the load without batteries through a grid outage.
A diesel rotary UPS puts on a single shaft a permanently spinning alternator, a flywheel that stores kinetic energy, and a diesel engine that can be clutched in. While the grid is present, the machine spins and conditions the power. When the grid drops, the flywheel supplies a few seconds of energy while the diesel starts and engages, with no battery rooms involved. The machine takes up little space, has no batteries to replace and monitor, and its high unit rating suits large sites. Its limit lies in that ride-through of a few seconds, which leaves a very thin margin for error. The machine also stays tied to the grid and absorbs its disturbances. And a mechanical failure or a fault on its high-voltage breaker drops the whole load it carries at once. That is why, in a risk assessment, the architecture around it weighs more than the technology itself: the number of units, and whether each piece of equipment is fed by two separate paths.
On Saturday, September 10, 2016, at around 11 a.m., the high-voltage breaker of one of the diesel rotary UPS units at the Global Switch 2 site in London developed a fault. Three floors lost power for 222 milliseconds. According to the trade press, the two feeds of the hosting provider Claranet both depended on the same chain, and it had restored only 85 percent of its services by around 5 p.m. The site ran for two days on utility power alone, with no backup.
Follow the research
One letter a week. First, the week's underwriting note when one is published, with its dated, reasoned decision. Then what the observatory published on cyber, artificial intelligence, insurance and reinsurance. No account, no tracking.
No spam, one-click unsubscribe, no data ever sold.